Diagnostics and fault elimination
17.6
Error codes, causes and remedies
The following table contains the most important error codes of the inverter in ascending
order.
Clicking the error code shows you a detailed description of the error message.
•
If the inverter indicates an «internal error» that is not listed here, restart the inverter. If the
•
error persists, make a note of the error code and contact the manufacturer.
Error code
Error message
8784
0x2250
CiA: Continuous over current (internal)
8992
0x2320
CiA: Short circuit/earth leakage (internal)
9024
0x2340
CiA: Short circuit (device internal)
9040
0x2350
CiA: i²*t overload (thermal state)
9090
0x2382
I*t error
9091
0x2383
I*t warning
9095
0x2387
Imax: Clamp responded too often
9096
0x2388
SL-PSM stall detection active
9098
0x238A
Maximum current reached
12576
0x3120
Mains phase fault
12672
0x3180
UPS operation active
12816
0x3210
DC bus overvoltage
12817
0x3211
DC bus overvoltage warning
12832
0x3220
DC bus undervoltage
12833
0x3221
DC bus undervoltage warning
12834
0x3222
DC-bus voltage to low for power up
16912
0x4210
PU: overtemperature fault
17024
0x4280
Heat sink temperature sensor fault
17025
0x4281
Heat sink fan warning
17029
0x4285
PU overtemperature warning
17168
0x4310
Motor temperature error
20754
0x5112
24 V supply critical
20864
0x5180
Overload 24 V supply
21376
0x5380
OEM hardware incompatible
24970
0x618A
Internal fan warning
25216
0x6280
Trigger/functions connected incorrectly
25217
0x6281
User-defined fault 1
25218
0x6282
User-defined fault 2
25232
0x6290
Warning invert rotation
25233
0x6291
Maximuml allowed troubles exceeded
25248
0x62A0
User-defined fault (LECOM)
25249
0x62A1
Network: user fault 1
25250
0x62A2
Network: user fault 2
25265
0x62B1
NetWordIN1 configuration incorrect
25505
0x63A1
CU: load error ID tag
25506
0x63A2
PU: load error ID tag
25507
0x63A3
Power unit unknown
28800
0x7080
Assertion level monitoring (Low/High)
28801
0x7081
Analog input 1 fault
28802
0x7082
Analog input 2 fault
28803
0x7083
HTL input fault
28833
0x70A1
Analog output 1 fault
28834
0x70A2
Analog output 2 fault
28961
0x7121
Pole position identification fault
29056
0x7180
Motor overcurrent
29445
0x7305
Encoder open circuit
29573
0x7385
Feedback system: speed limit
30336
0x7680
Memory module is full
616
Error type
Configurable in
Fault
—
Fault
—
Fault
—
Fault
0x2D4B:003 (P308.03)
Fault
0x2D40:005 (P135.05)
Warning
—
Fault
—
Trouble
—
Information
—
Fault
—
Warning
—
Fault
—
Warning
—
Trouble
—
Warning
—
Warning
—
Fault
—
Fault
—
Warning
—
Warning
—
Fault
0x2D49:002 (P309.02)
Warning
—
Warning
—
Fault
—
Warning
—
Trouble
—
Fault
—
Fault
—
Warning
—
Fault
—
Fault
—
Fault
—
Fault
—
Trouble
—
Fault
—
Fault
—
Fault
—
Fault
—
Fault
0x2636:010 (P430.10)
Fault
0x2637:010 (P431.10)
No response
0x2641:006 (P416.06)
Warning
—
Warning
—
Fault
0x2C60
Fault
0x2D46:002 (P353.02)
Warning
0x2C45 (P342.00)
Warning
—
Warning
—

К сожалению, в процессе эксплуатации выходит из строя даже самое надежное промышленное оборудование. В данной статье мы разберем частотный преобразователь Lenze, а точнее коды ошибок частотного преобразователя Lenze 8200 SMD и TMD, коды ошибок и их расшифровка. Частотники в наше время нашли широкое применения в абсолютно всех сферах промышленности управляя как мини моторами в оргтехнике, так и гигантскими двигателями в горнодобывающей промышленности.

Коды ошибок частотных преобразователей у каждого производителя свои при этом коды ошибок могут отличатся даже у одного и того же производителя, разные принципы работы или серия ЧП.
Существует несколько видов ошибок, некоторые из них можно устранить автоматически, а некоторые возможно исправить только, обратившись в специализированный сервисный центр. В таблицах ниже приведены все коды ошибок частотного преобразователя Lenze и их расшифровка, то есть причина по которой возникла та или иная ошибка.
Коды ошибок частотного преобразователя Lenze серии SMD
Коды ошибок частотного преобразователя Lenze SMD, информирующие о состоянии привода.
|
Сообщение об ошибке |
Причина |
Исправление |
|
|
Код ошибки |
Описание ошибки |
||
|
50.0 |
Выходная частота. |
Безаварийная работа. |
|
|
OFF |
Стоп. На выходных клеммах U,V,W нет напряжения. |
Низкий уровень на клемме 28. |
|
|
Inh |
Блокировка преобразователя частоты. На выходных клеммах U,V,W нет напряжения. |
Привод настроен на управление от удаленного пульта или через последовательный порт. |
|
|
StP |
Выходная частота 0Гц. На выходных клеммах U,V,W нет напряжения. |
Заданная частота равна 0 (С31 = 0). |
|
|
Активирована функция «Быстрый останов» |
|
||
|
br |
Торможение постоянным током. |
Активирована функция «Торможение DC» |
|
|
CL |
Достигнут предел ограничения тока. |
Контролируемая перегрузка. |
|
|
LU |
Недостаточное напряжение. |
Слишком низкое напряжение питающей сети. |
|
|
dEC |
Перенапряжение при Торможении. |
Слишком интенсивное торможение или большая нагрузка. |
|
|
nEd |
Нет доступа к кодам. |
Выйти из этого режима можно только остановив привод. |
|
|
rC |
Активен удаленный пульт. |
Попытка использовать кнопку на панели контроллера. |
|
В отличии от верхней таблицы коды которой больше показывают состояние привода, в нижней таблице представлены все коды ошибок ЧП Lenze с подробными пояснениями по их устранению.
Коды ошибок частотного преобразователя Lenze SMD и их расшифровка.
|
Сообщение об ошибке |
Причина |
Исправление |
|
|
Код ошибки |
Описание ошибки |
||
|
cF |
Ошибка данных |
Неверные данные. |
|
|
CF |
Ошибка данных. |
||
|
FI |
Ошибка EPM |
ЕРМ «завис» либо неисправен. |
|
|
CFG |
Неоднозначная конфигурация |
Входам E1…E3 присвоены одинаковые функции. |
|
|
Включена функция или UP или DOWN. |
|
||
|
dF |
Ошибка динамического торможения |
Перегрев резистора динамического торможения. |
|
|
EEr |
Внешняя ошибка |
Триггер «Авария» активен СЕ1..3 = 10. |
|
|
F2 FO |
Внутренняя ошибка |
|
|
|
FС3 |
Ошибка коммуникации |
Вышло время ожидания таймера. |
|
|
FС5 |
Ошибка коммуникации |
Ошибка последовательного соединения. |
|
|
JF |
Ошибка удаленного пульта |
Пульт не подсоединён. |
|
|
LC |
Блокировка автоматического пуска |
c42 = 0. |
|
|
OC1 |
Короткое замыкание или перегрузка частотного преобразователя |
Короткое замыкание. |
|
|
Слишком высокое емкостное сопротивление кабеля двигателя. |
|
||
|
Задано слишком малое время разгона C12. |
|
||
|
Дефекты кабеля двигателя. |
|
||
|
Неисправность двигателя. |
|
||
|
Частая и длительная перегрузка. |
|
||
|
OC2 |
Замыкание на землю |
Замыкание на землю на выходе преобразователя частоты. |
|
|
OC6 |
Перегрузка двигателя |
Перегрузка из-за слишком большого значения I2t. Слишком частые или длительные режимы торможения и ускорения. |
|
|
OH |
Перегрев частотного преобразователя |
Повышенная температура преобразователя частоты. |
|
|
OU |
Перегрузка по цепям постоянного тока |
Сетевое напряжение завышено. |
|
|
Слишком маленькое время торможения. |
|
||
|
rSt |
Невозможен автоматический сброс триггера «Авария» |
Более 8 ошибок за 10 мин. |
|
|
SdS |
Потеря сигнала 4-20мА |
Сигнал менее 2мА при 4 – 20мА. |
|
|
SF |
Обрыв одной фазы |
Обрыв питающей фазы. |
|
В некоторых случаях могут понадобится принципиальные схемы по подключению частотного преобразователя Lenze это особенно актуально по прошествии определенного времени, когда данное оборудование производитель снимет с производства и в случае отсутствия документации взять информацию буде неоткуда.
Коды ошибок частотного преобразователя Lenze серии TMD
Как уже было описано выше коды шибок частотных преобразователей могут отличаться даже у одного и тогоже производителя, в данном случае Lenze и преобразователи отличаются серией, выше была описана серия SMD сейчас мы рассмотрим коды ошибок частотного преобразователя Lenze серии TMD.
Коды ошибок частотного преобразователя Lenze TMD, информирующие о состоянии привода.
|
Сообщение об ошибке |
Причина |
Исправление |
|
|
Код ошибки |
Описание ошибки |
||
|
e.g.50.0 |
Выходная частота. |
Безаварийная работа. |
|
|
OFF |
Стоп. |
Низкий уровень на клемме 28. |
|
|
Inh |
Запрет по выходам U,V,W. |
Отсутствует установка задания. |
|
|
StP |
Выходная частота 0Гц. |
Заданная частота равна 0. |
|
|
Активирована функция «Быстрый останов» |
|
||
|
FSt |
Попытка быстрого рестарта после ошибки. |
c42 = 2, 3 |
|
|
br |
Торможение постоянным током. |
Активирована функция «Торможение DC» |
|
|
CAL |
Процесс автонастройки. |
с48 = 1 и клемма 28 = HIGH |
|
|
CL, FCL |
Достигнут предел ограничения тока. |
Контролируемая перегрузка. |
|
|
LU |
Низкое напряжение. |
Слишком низкое напряжение питающей сети. |
Проверьте напряжение питающей сети. |
|
dEC |
Перенапряжение при Торможении. |
Слишком интенсивное торможение или большая нагрузка. |
|
|
nEd |
Нет доступа к кодам. |
Выйти из этого режима можно только остановив привод. |
|
|
rC |
Активен удаленный пульт. |
Попытка использовать кнопку на панели контроллера. |
|
В отличии от верхней таблицы коды которой больше показывают состояние привода, в нижней таблице представлены все коды ошибок ЧП Lenze с подробными пояснениями по их устранению.
Коды ошибок частотного преобразователя Lenze TMD и их расшифровка.
|
Сообщение об ошибке |
Причина |
Исправление |
|
|
Код ошибки |
Описание ошибки |
||
|
Ad |
Ошибка частотного преобразователя A/D |
|
|
|
bF |
Ошибка идентификации. |
Данные С93 не соответствуют приводу. |
|
|
cF |
Ошибка данных. |
Неверные данные |
|
|
CF |
Ошибка данных |
||
|
GF |
Данные с ПК неверны |
||
|
FI |
Ошибка привода. |
Частотный преобразователь «завис» / неисправен. |
|
|
CFG |
Неоднозначная конфигурация. |
Входам E1…E4 присвоены одинаковые функции. |
|
|
Включена функция UP или DOWN |
|
||
|
dF |
Ошибка динамического торможения. |
Перегрев резистора динамического торможения. |
|
|
LC |
Блокировка автоматического пуска |
c42 = 0 |
|
|
EEr |
Внешняя ошибка |
Триггер «Авария» активен. |
|
|
F2..FO |
Внутренняя ошибка |
|
|
|
FC3, FC5 |
Ошибка коммуникации. |
|
|
|
JF |
Ошибка в удаленной клавиатуре. |
Клавиатура не подключена. |
|
|
nId |
Ошибка автонастройки. |
Попытка автонастройки перед установкой параметров С86..С91. |
|
|
OC1 |
Короткое замыкание или перегрузка частотного преобразователя. |
Короткое замыкание. |
|
|
Задано слишком малое время разгона C12. |
|
||
|
Дефекты кабеля двигателя. |
|
||
|
Неисправность двигателя. |
|
||
|
Частая и длительная перегрузка. |
|
||
|
OC2 |
Замыкание на землю. |
Замыкание на землю на выходе преобразователя частоты. |
|
|
OC6 |
Перегрузка двигателя. |
Перегрузка из-за слишком большого значения I2t. Слишком частые или длительные режимы торможения и ускорения. |
|
|
LP1 |
Обрыв фазы мотора. |
Разомкнутая цепь на выходе привода. |
|
|
OH |
Перегрев частотного преобразователя. |
Повышенная температура преобразователя частоты. |
|
|
OU |
Перегрузка по цепям |
Завышенное сетевое напряжение. |
|
|
Малое время торможения. |
|
||
|
rF |
Ошибка подхвата |
Привод не может синхронизироваться с мотором во время подхвата. |
|
|
rSt |
Невозможен автоматический сброс триггера «Авария» |
Более 8 ошибок за 10 мин. |
|
|
SdS |
Ошибка токового задания |
Аналоговый сигнал < 2 мА (С34 = 5). |
|
|
SF |
Обрыв одной фазы |
Обрыв фазы питания. |
|
Сброс ошибок и Ремонт частотников в сервисном центре
Компания «Кернел» производит ремонт промышленной электроники и оборудования с 2002 года. За это время мы накопили колоссальный опыт в том числе опыт в ремонте частотных преобразователей Lenze серии SMD и TMD. 
Специалисты нашего сервисного центра уделяют максимальное внимание к качеству исполнения ремонта, программирования и настройке промышленного преобразователя частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на все выполненные работы шесть месяцев.
Ремонт промышленной электроники производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного оборудования, квалифицированным персоналом с инженерным образованием.
Если на вашем производстве появились проблемы с частотным преобразователем, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Обращайтесь в сервисный центр «Кернел». Специалисты нашей компании в минимальные сроки проведут глубокую диагностику и последующий ремонт частотного преобразователя. Оставьте заказ на ремонт оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.
Как с нами связаться
У вас остались вопросы, связанные с ремонтом, программированием и настройкой частотного преобразователя Lenze? Задайте их нашим менеджерам. Связаться с ними можно несколькими способами:
- Заказав обратный звонок (кнопка в правом нижнем углу сайта)
- Посредством чата (кнопка расположена с левой стороны сайта)
- Либо позвонив по номеру: +7(8482) 79-78-54; +7(917) 121-53-01
- Написав на электронную почту: 89171215301@mail.ru
Далеко не полный список производителей промышленной электроники и оборудования, ремонтируемой в нашей компании.
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
Operating Instructions | US
Inverter
i550 protec IP31, IP66/NEMA 1, NEMA 4X outdoor
0.5 … 15 hp
(0.37 … 11 kW)
As easy as that.
Related Manuals for Lenze i550
Summary of Contents for Lenze i550
-
Page 1
Operating Instructions | US Inverter i550 protec IP31, IP66/NEMA 1, NEMA 4X outdoor 0.5 … 15 hp (0.37 … 11 kW) As easy as that. -
Page 2
Inverter status LEDs Relay output Diagnos c interface Micro-USB Safety module Shield connec on Slot Control cable X100 Mains connec on X105 Motor connec on Brake resistor connec on DC bus Cable glands with shield connec on Operating Instructions i550 protec… -
Page 3: Table Of Contents
6.6 1-phase mains connection 120 V …………… 12 6.7 1-phase mains connection 230/240 V …………..13 6.8 3-phase mains connection 230/240 V …………..14 6.9 3-phase mains connection 400 V …………… 15 6.10 3-phase mains connection 480 V …………… 16 Operating Instructions i550 protec…
-
Page 4: General Information
The i500 product family is designed for the power range of 0.5 … 15 hp. meets the regulations of NFPA 79 (machinery safety – US), Z432 The inverter i550 protec is suitable for conveyors, packaging equipment (machinery safety – Canada), NFPA 70 (US National Electrical Code) plus fan and pump systems.
-
Page 5: Identification Of The Products
(examples) Standard I/O with CANopen 002S be checked. Lenze does not take responsibility for the suitability of the Standard I/O with Modbus RTU 003S process and circuit proposals. Standard I/O with EtherCAT…
-
Page 6: Layout Of Warning Notices
180°/number of pole pairs on the motor may occur NOTICE (e.g. 4-pole motor): residual movement max. 180°/2 = 90°). Indicates a material hazard. If this instruction is ignored, material damages may result. Operating Instructions i550 protec…
-
Page 7: Technical Data
Max. output frequency 0 Hz … 599 Hz Overload capacity 200 % for 3 s; (120-V network and 230-V network) 150 % for 60 s Overload capacity 200 % for 3 s (400-V network and 480-V network) Operating Instructions i550 protec…
-
Page 8: Mechanical Installation
5.91 >1.97 >1.97 7.5 … 11 Device height Hole spacing over center of device Device width (Bottom screws not visible in the illustration) Device depth Top mounting clearance Hole dimension for top/bottom fixing Bottom mounting clearance Operating Instructions i550 protec…
-
Page 9: Cable Entries With Shield Support
Cable entry A Cable entry B Cable entry C Operation with cable gland M20 x 1.5 M12 x 1.5 M32 x 1.5 Max. external cable diameter without cable gland Max. external cable diameter Also see “EMC-compliant installation“. Operating Instructions i550 protec…
-
Page 10: Electrical Installation
Control terminals (C-core/core/C-core/shield < 75/150 pF/m ≥ AWG 14; +24 V +10 V C-core/core/C-core/shield 100 mA < 150/300 pF/m ≤ AWG 12) E Power supply » » » DC 24 V SELV/PELV (+19.2 … +28.8 V) Operating Instructions i550 protec…
-
Page 11: Control Terminals
PTC or thermal contact X109 Connection type Spring terminal Terminal T1 Max. cable cross-section Stripping length 0.35 Terminal T2 Tightening torque lb-in Sensor types PTC single sensor PTC triplet sensor Tools required 3/32 x 0.02 Thermal contact Operating Instructions i550 protec…
-
Page 12: 1-Phase Mains Connection 120 V
Fuse SCCR Characteristic all acc. to UL248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 1-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 13: 1-Phase Mains Connection 230/240 V
AC 170 V … 264 V Max. rated current 45 Hz … 65 Hz Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker Motor connection 1-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 14: 3-Phase Mains Connection 230/240 V
Fuse SCCR all acc. to UL 248/Class CF, J, T Characteristic Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 15: 3-Phase Mains Connection 400 V
SCCR Characterisctic all acc. to UL 248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 16: 3-Phase Mains Connection 480 V
SCCR Characterisctic all acc. to UL 248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 17: Commissioning
Commissioning Commissioning Keypad module The inverter i550 protec can be ordered from factory with the following Initial switch-on accessories instead of the keypad module: • WLAN module DANGER • without module Electrical voltage Incorrect wiring can cause unexpected states during the commissioning phase.
-
Page 18: Functions Of The Keys
DO1 func on • Preset 1 is activated if DI4 is connected. P420.02 • Preset 2 is activated if DI5 is connected. • Preset 3 is activated if DI4 and DI5 are connected at the same time. Operating Instructions i550 protec…
-
Page 19: Extended Terminal Control
1. Press the key to start the motor. terminals (X3, X9 and X109) linked with the respective parameters. • The keypad shows the motor speed. Optional external 24-V-supply (i550 only) 2. Use the key or the key to change the frequency setpoint.
-
Page 20: The Most Important Parameters At A Glance
The setpoint is defined as process data object via the network. Frequency preset 1 … 15 [11] … [25] For the setpoint selection, “preset” values can be parameterized and selected. All frequency presets are described in detail in the commissioning manual. http://www.Lenze.com * Default setting dependent on the model Operating Instructions i550 protec…
-
Page 21
V/f characteristic control The control mode is used for speed control of an asynchronous motor via a V/f characteristic with speed feedback. (VFC closed loop) This motor control mode is described in the commissioning manual. http://www.Lenze.com P302.00 V/f characteristic Linear Linear characteristic for drives with constant load torque over the speed. -
Page 22
Run forward Not connected Assignment of a trigger to the “Run forward (CW)” function. Trigger = TRUE: Let motor rotate forward. Trigger = FALSE: Stop motor. Stop via P400.01 (default setting of digital input 1). * Default setting dependent on the model Operating Instructions i550 protec… -
Page 23
• The standard setpoint source for operating mode is selected in P201.01. P440.01 AO1 output area Inhibited Definition of the output range. 0 … 10 VDC 0 … 5 VDC 2 … 10 VDC 4 … 20 mA 0 … 20 mA * Default setting dependent on the model Operating Instructions i550 protec… -
Page 24: Group 2: Basic Setting
(non-energized) • A default inverter characteristic is loaded. • The motor equivalent circuit diagram data and controller settings are calculated on the basis of the currently set rated motor data. • The motor is not energized. Operating Instructions i550 protec…
-
Page 25: Group 7: Additional Functions
• Do not switch off the supply voltage during the saving process and do not unplug the memory module from the inverter! Action cancelled • When the inverter is switched on, all parameters are automatically loaded from the user memory of the memory module to No access the RAM memory of the inverter. No access (Inverter disabled) Operating Instructions i550 protec…
-
Page 26: Troubleshooting
2. Via P400.04 (default setting of digital input 2). • Cause of error has been eliminated and no blocking time is active. • The error is reset if a signal is applied to digital input 2 (P400.04). Operating Instructions i550 protec…
-
Page 27: Error Codes
• Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed. 4310 Error: Motor overtemperature Fault • Check drive sizing. • Check motor thermal sensor and wiring (X109/T1 and X109/T2). Operating Instructions i550 protec…
-
Page 28
Note! The warning will be reset if the thermal load falls below the warning threshold (P707.08) of — 20 %. FF37 Automatic start disabled Fault • Deactivate start command and reset error. FF85 Keypad full control active Warning • To exit the control mode, press the keypad key. Operating Instructions i550 protec… -
Page 29: Led Status
Fundamental information on project planning and ordering the product Commissioning document Fundamental information for the installation and commissioning of the product Mounting instructions Fundamental information on mounting the product The documents can be found online: http://www.Lenze.com Operating Instructions i550 protec…
-
Page 30
© 01/2020 | 2.0 Lenze Drives GmbH Postfach 101352, 31763 Hameln Breslauer Straße 3, 32699 Extertal GERMANY HR Lemgo B 6478 Phone +49 5154 82-0 Fax +49 5154 82-2800 sales.de@lenze.com www.Lenze.com Lenze Service GmbH Breslauer Straße 3, 32699 Extertal GERMANY…
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
Operating Instructions | US
Inverter
i550 protec IP31, IP66/NEMA 1, NEMA 4X outdoor
0.5 … 15 hp
(0.37 … 11 kW)
As easy as that.
Related Manuals for Lenze i550
Summary of Contents for Lenze i550
-
Page 1
Operating Instructions | US Inverter i550 protec IP31, IP66/NEMA 1, NEMA 4X outdoor 0.5 … 15 hp (0.37 … 11 kW) As easy as that. -
Page 2
Inverter status LEDs Relay output Diagnos c interface Micro-USB Safety module Shield connec on Slot Control cable X100 Mains connec on X105 Motor connec on Brake resistor connec on DC bus Cable glands with shield connec on Operating Instructions i550 protec… -
Page 3: Table Of Contents
6.6 1-phase mains connection 120 V …………… 12 6.7 1-phase mains connection 230/240 V …………..13 6.8 3-phase mains connection 230/240 V …………..14 6.9 3-phase mains connection 400 V …………… 15 6.10 3-phase mains connection 480 V …………… 16 Operating Instructions i550 protec…
-
Page 4: General Information
The i500 product family is designed for the power range of 0.5 … 15 hp. meets the regulations of NFPA 79 (machinery safety – US), Z432 The inverter i550 protec is suitable for conveyors, packaging equipment (machinery safety – Canada), NFPA 70 (US National Electrical Code) plus fan and pump systems.
-
Page 5: Identification Of The Products
(examples) Standard I/O with CANopen 002S be checked. Lenze does not take responsibility for the suitability of the Standard I/O with Modbus RTU 003S process and circuit proposals. Standard I/O with EtherCAT…
-
Page 6: Layout Of Warning Notices
180°/number of pole pairs on the motor may occur NOTICE (e.g. 4-pole motor): residual movement max. 180°/2 = 90°). Indicates a material hazard. If this instruction is ignored, material damages may result. Operating Instructions i550 protec…
-
Page 7: Technical Data
Max. output frequency 0 Hz … 599 Hz Overload capacity 200 % for 3 s; (120-V network and 230-V network) 150 % for 60 s Overload capacity 200 % for 3 s (400-V network and 480-V network) Operating Instructions i550 protec…
-
Page 8: Mechanical Installation
5.91 >1.97 >1.97 7.5 … 11 Device height Hole spacing over center of device Device width (Bottom screws not visible in the illustration) Device depth Top mounting clearance Hole dimension for top/bottom fixing Bottom mounting clearance Operating Instructions i550 protec…
-
Page 9: Cable Entries With Shield Support
Cable entry A Cable entry B Cable entry C Operation with cable gland M20 x 1.5 M12 x 1.5 M32 x 1.5 Max. external cable diameter without cable gland Max. external cable diameter Also see “EMC-compliant installation“. Operating Instructions i550 protec…
-
Page 10: Electrical Installation
Control terminals (C-core/core/C-core/shield < 75/150 pF/m ≥ AWG 14; +24 V +10 V C-core/core/C-core/shield 100 mA < 150/300 pF/m ≤ AWG 12) E Power supply » » » DC 24 V SELV/PELV (+19.2 … +28.8 V) Operating Instructions i550 protec…
-
Page 11: Control Terminals
PTC or thermal contact X109 Connection type Spring terminal Terminal T1 Max. cable cross-section Stripping length 0.35 Terminal T2 Tightening torque lb-in Sensor types PTC single sensor PTC triplet sensor Tools required 3/32 x 0.02 Thermal contact Operating Instructions i550 protec…
-
Page 12: 1-Phase Mains Connection 120 V
Fuse SCCR Characteristic all acc. to UL248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 1-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 13: 1-Phase Mains Connection 230/240 V
AC 170 V … 264 V Max. rated current 45 Hz … 65 Hz Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker Motor connection 1-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 14: 3-Phase Mains Connection 230/240 V
Fuse SCCR all acc. to UL 248/Class CF, J, T Characteristic Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 15: 3-Phase Mains Connection 400 V
SCCR Characterisctic all acc. to UL 248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 16: 3-Phase Mains Connection 480 V
SCCR Characterisctic all acc. to UL 248/Class CC, CF, J, T Max. rated current Circuit breaker SCCR Characteristic all acc. to UL 489 Max. rated current Earth-leakage circuit breaker 3-phase mains connection ≥30 mA, type B Operating Instructions i550 protec…
-
Page 17: Commissioning
Commissioning Commissioning Keypad module The inverter i550 protec can be ordered from factory with the following Initial switch-on accessories instead of the keypad module: • WLAN module DANGER • without module Electrical voltage Incorrect wiring can cause unexpected states during the commissioning phase.
-
Page 18: Functions Of The Keys
DO1 func on • Preset 1 is activated if DI4 is connected. P420.02 • Preset 2 is activated if DI5 is connected. • Preset 3 is activated if DI4 and DI5 are connected at the same time. Operating Instructions i550 protec…
-
Page 19: Extended Terminal Control
1. Press the key to start the motor. terminals (X3, X9 and X109) linked with the respective parameters. • The keypad shows the motor speed. Optional external 24-V-supply (i550 only) 2. Use the key or the key to change the frequency setpoint.
-
Page 20: The Most Important Parameters At A Glance
The setpoint is defined as process data object via the network. Frequency preset 1 … 15 [11] … [25] For the setpoint selection, “preset” values can be parameterized and selected. All frequency presets are described in detail in the commissioning manual. http://www.Lenze.com * Default setting dependent on the model Operating Instructions i550 protec…
-
Page 21
V/f characteristic control The control mode is used for speed control of an asynchronous motor via a V/f characteristic with speed feedback. (VFC closed loop) This motor control mode is described in the commissioning manual. http://www.Lenze.com P302.00 V/f characteristic Linear Linear characteristic for drives with constant load torque over the speed. -
Page 22
Run forward Not connected Assignment of a trigger to the “Run forward (CW)” function. Trigger = TRUE: Let motor rotate forward. Trigger = FALSE: Stop motor. Stop via P400.01 (default setting of digital input 1). * Default setting dependent on the model Operating Instructions i550 protec… -
Page 23
• The standard setpoint source for operating mode is selected in P201.01. P440.01 AO1 output area Inhibited Definition of the output range. 0 … 10 VDC 0 … 5 VDC 2 … 10 VDC 4 … 20 mA 0 … 20 mA * Default setting dependent on the model Operating Instructions i550 protec… -
Page 24: Group 2: Basic Setting
(non-energized) • A default inverter characteristic is loaded. • The motor equivalent circuit diagram data and controller settings are calculated on the basis of the currently set rated motor data. • The motor is not energized. Operating Instructions i550 protec…
-
Page 25: Group 7: Additional Functions
• Do not switch off the supply voltage during the saving process and do not unplug the memory module from the inverter! Action cancelled • When the inverter is switched on, all parameters are automatically loaded from the user memory of the memory module to No access the RAM memory of the inverter. No access (Inverter disabled) Operating Instructions i550 protec…
-
Page 26: Troubleshooting
2. Via P400.04 (default setting of digital input 2). • Cause of error has been eliminated and no blocking time is active. • The error is reset if a signal is applied to digital input 2 (P400.04). Operating Instructions i550 protec…
-
Page 27: Error Codes
• Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed. 4310 Error: Motor overtemperature Fault • Check drive sizing. • Check motor thermal sensor and wiring (X109/T1 and X109/T2). Operating Instructions i550 protec…
-
Page 28
Note! The warning will be reset if the thermal load falls below the warning threshold (P707.08) of — 20 %. FF37 Automatic start disabled Fault • Deactivate start command and reset error. FF85 Keypad full control active Warning • To exit the control mode, press the keypad key. Operating Instructions i550 protec… -
Page 29: Led Status
Fundamental information on project planning and ordering the product Commissioning document Fundamental information for the installation and commissioning of the product Mounting instructions Fundamental information on mounting the product The documents can be found online: http://www.Lenze.com Operating Instructions i550 protec…
-
Page 30
© 01/2020 | 2.0 Lenze Drives GmbH Postfach 101352, 31763 Hameln Breslauer Straße 3, 32699 Extertal GERMANY HR Lemgo B 6478 Phone +49 5154 82-0 Fax +49 5154 82-2800 sales.de@lenze.com www.Lenze.com Lenze Service GmbH Breslauer Straße 3, 32699 Extertal GERMANY…